Contact Us +86-0592-8105999
Evada HQ-M Series Modular UPS Powers Up the New Electrical System Mar 14, 2023

At the beginning of 2019, State Grid Corporation of China (SGCC) has put forward the strategic goal of ”Three Types and Two Networks, World-Class”, it aims to build out Ubiquitous Electric Internet of Things (UEIOT) on the basis of Strong Smart Grid, and to shape interchanging, platforming, sharing, modern business.


Evada Modular UPS powers up the SGCC‘s new electrical system


This project covers a total area of about 19,500 square meters. The new system can run 8 computer labs and Uninterruptible Power Supply (UPS) of Cyber Security Centre, Dispatch Centre, Customer Service Centre and Administrative Centre.


Evada Modular UPS powers up the SGCC‘s new electrical system


Data center infrastructure is significant to business’s safe and secure, it carries this critical business to move forward. In this case, Evada has supplied its HQ-M Series Modular UPS to the SGCC, which includes 8 sets of 500KVA and 4 sets of 400KVA, both are configured with the latest Lithium iron phosphate Battery System to support the decarbonization.


Evada HQ-M Series Modular UPS

Evada HQ-M Series Modular UPS


1. Vertical Scalability

- Bypass switch and power module both are hot-swappable, maintenance time is within 5 minutes

- Dual input design ensuring seamless operation without taking any extra floor space


2. Parallel Expansion

- Allowing users to customize the number of power modules based on their power demands

- N+X redundancy design, starts out with 20% extra capacity

- Decentralized modular technology enables the power modules to work without the risk of a ”single point of failure”, guaranteed autonomous operation


3. ECO Friendly

- Output power factor = 1

- ECO mode to save energy costs, to achieve high energy efficiency up to 99% and improve the UPS system efficiency by 10%

- ECO mode implements active harmonic compensation

- Automatically detects power fluctuations of the bypass input


4. Smart Management

- The 10” LCD touch screen, communication slots, along with the dedicated service ports, the integration into any building management system and data center infrastructure management (DCIM), ensure the control and monitoring is easy

- Smart sleep function utilize energy internal circle technology to increase total load rate and to achieve higher efficiency

- Fan speed varies intelligently with temperature, extending the lifespan of the consumables


Evada HQ-M Series Modular UPS

Evada HQ-M Series Modular UPS(1200kVA and 500kVA/600kVA


”Three Types and Two Networks” is SGCC’s gesture to rise with the occasion of the energy revolution and the digital revolution. To support this gesture, Evada draws on the experience from the past 25 years, combines with actual demand, makes sure the application will be extended to more settings. Evada has been trying to provide a strong underpinning for the digitization of power grid and empower the new electricity system to build an energy ecosphere.



Evada HQ-M Series Modular UPS technical specifications

Model

HQ-M300/50

HQ-M500/50

HQ-M600/60

HQ-M840/60

HQ-M1000/50

HQ-M1200/60

Rated Capacity

300kVA

500kVA

600kVA

840kVA

1000kVA

1200kVA

Power Module Capacity

50kVA

60kVA

50kVA

60kVA

Input

Wiring Method

3 Phase+N+PE

Rated Voltage

380/400/415VAC(line-line)

Rated Frequency

50/60Hz

Voltage Range

304VAC ~ 478VAC (line-line) full load304VAC ~ 228VAC(line-line) load derating linearly from 100% to 80%

Frequency Range

40Hz~70Hz

Power Factor

>0.99

THD

THD3%(linear full load); THD5%(non-linear full load)

Bypass

Rated Voltage

380/400/415VAC(line voltage)

Voltage Range

Factory setting -20% ~ +15% settable, upper limit:+10%,+15%,+20%,+25%lower limit:-10%,-15%, -20%, -30%,-40%

Frequency Range

Settable ( ±1Hz ±3Hz ±5Hz)

Overload Capacity

110% for long run,>150% for 200ms

Battery

Battery Voltage

±192VDC ( 384 ~ 528VDC 32 ~ 44 block settable factory setting 32 block)

Charging Capacity

15%* total capacity

Voltage Accuracy

±1%

Output

Rated Voltage

380V/400V/415V(line-line)

Power Factor

1

Rated Frequency

50/60Hz

Voltage Accuracy

≤±1.0%@ balanced load≤±5.0%@ unbalanced load

Frequency Accuracy

50/60Hz±0.01%

Frequency Tracking Range

Settable ±0.5Hz~±5Hz ; factory setting±3Hz

THD

THDu≤2%(100% linear load),THDu≤4%( nonlinear load)

Three-phase Phase Accuracy

120°±1°

Crest Factor

3:1

Overload

105%, long run;    <110%, 60mins110 ~ 125%, 10mins;    >125 ~ 150%, 1mins;    >150%, 200ms

System

Efficiency

96.5%@ double conversion mode

Display

Super large color touch screen +LED

Wiring

Support top in and bottom in

Standard

IEC62040-1-1; IEC62040-2; IEC62040-3

Protection Class

IP20

Optional

SNMP cardmodbus cardparallel components, lightning protection components, dust-proof net, LBS, editable dry contact

Working Condition

Temperature 0~40℃; humidity0~95%( no condensation)

Noise

65dB @ 1meter

Altitude

<1000 meters, no derating, 1000 meters, derating 1% if every 100 meters increased

Cabinet Type

6+1 Modules

10+2 Modules

12 Modules

14 Modules

20 Modules

20 Modules

Size

System W x D x H (mm)

600 x 1100 x 2000

1000 x 1100 x 2000

1600 x 900 x 2000

2000 x 1100 x 2000

Module W x D x H (mm)

440 x 720 x 130 (3U)

Weight

System(kg)

250

500

530

980

1100

1180

Module(kg)

38

Subscribe To Our Newsletter