eLite Pro Solar Energy Hybrid Inverter
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
The 3-5kW single-phase off grid inverter is an all-in-one system for supplying solar power at home. It can be flexibly configured to single-phase or three-phase
Application: Computer, data center, telecom, finance, security, transportation, medical, petrochemical, etc.
ABOUT HQ-M ONLINE THREE PHASE MODULAR UPS
EVADA HQ-M Three Phase Modular UPS, with a 25kVA UPS capacity (available in the range of 10kVA to 300kVA) is a versatile solution. This modular online UPS, featuring a double conversion design, serves as a perfect back UPS for various applications. The EVADA HQ-M Modular UPS combines double conversion online UPS capability and 3 phase modular UPS scalability, offers easy expansion and customization.
◆FEATURE
Intelligent Flexibility
*Hot-swappable bypass/power module
*30-44 units battery configurable
*Allowing common battery group for parallel
*7" Color touchscreen
*Cold start function
High Reliability
*Distributed control system for power module
*Isolated air duct for key components
*BMS monitors battery information in real time
*Power module N+X redundancy design
Green Performance
*ECO mode for energy saving
*Efficiency up to 96%Output PF = 1
*Maintenance bypass mode
*THDi < 3% and input PF > 0.99
◆OTHER
N+X redundancy design
Three Phase Input, Three Phase Output
Capacity: 10kVA-300kVA
Online double conversion topology, high input PF>0.99
Battery management system continuously tracks and reports battery status and performance
SPECIFICATION
Model | HQ-M60 | HQ-M75 | HQ-M80 | HQ-M100 | HQ-M120 | HQ-M140 | HQ-M150 | HQ-M175 | HQ-M200 | HQ-M300 |
Capacity | 60kVA | 75kVA | 80kVA | 100kVA | 120kVA | 140kVA | 150kVA | 175kVA | 200kVA | 300kVA |
Cabinet Type | 4 Modules | 7 Modules | 12 Modules | |||||||
Power Module Capacity | 10/15/20kVA | 25kVA | 10/15/20kVA | 25kVA | 10/15/20kVA | 25kVA | 10/15/20kVA | 25kVA | ||
Input | ||||||||||
Rated Voltage | 3 Phase+N+PE 380/400/415VAC (Line voltage) | |||||||||
Rated Frequency | \50/60Hz | |||||||||
Voltage Range | 304~478VAC | |||||||||
Frequency Range (Full Load) | 40 ~ 70Hz | |||||||||
Power Factor | >0.99 | |||||||||
THDi | <3% (100% linear load); <5% (100% nonlinear load) | |||||||||
Output | ||||||||||
Rated Voltage | 380V/400V/415V(Line voltage) | |||||||||
Rated Frequency | 50/60Hz | |||||||||
Voltage Accuracy | ≤±1.0% @ balanced load;≤±5.0% @ unbalanced load | |||||||||
Frequency Accuracy | 50/60Hz ± 0.1% | |||||||||
Frequency Tracking Range | ±0.5Hz ~ ±5Hz, configurable, default: ±3Hz | |||||||||
Overload | ≤105%,long run; 105% ~ 110%,60min; 110 ~ 125%,10min;125~150%,1min; >150%,switch to the bypass immediately | |||||||||
Power Factor | 1 | |||||||||
THDu | ≤2% @ (100% linear load);≤4% @ (100% nonlinear load) | |||||||||
Crest Factor | 3:1 | |||||||||
Three-Phase Accuracy | 120° ± 1° | |||||||||
Bypass | ||||||||||
Rated Voltage | 380V/400V/415V(Line voltage) | |||||||||
Voltage Range | Default: -20% ~ +15%;configurable, upper limit: +10%, +15%, +20%, +25%;lower limit: -10%, -15%, -20%, -30%, -40% |