ABOUT DTH33 THREE PHASE ONLINE TOWER UPS
DTH33 10KVA-40KVA Three Phase Online Tower UPS is a reliable 3 Phase power supplies. With an uninterruptible power system and the multi switch UPS design enhances the flexibility. The EVADA DTH33 Three Phase Online Tower UPS provides dependable 15kVA UPS support (also including 10kVA/20kVA/25kVA), it’s ideal for industries requiring an unlimited power supply.
Applications: Communication, finance, security, data center, medical equipment, industrial control device.
◆FEATURE
Advanced Technology
*Wide input range
*50/60Hz Auto-sensing
*N+X parallel technology
*Automated self-testing
*Generator compatible
*Auto-restart on power return after low voltage shutdown
Outstanding Flexibility
*Multifunction LCD & LED readout and mains power start
*Cold start function
*Optional output isolation transformer
Green Performance
*ECO mode for energy saving
*PFC technology, input power factor ≥ 0.99
*Support RS232, RS485, dry contact or SNMP
◆OTHER
Input switch/maintenance switch/output switch included
3 Phase Input, 3 Phase Output
Capacity: 10kVA/15kVA/20kVA/25kVA
Inverter mode efficiency: 95%, ECO mode efficiency: 99%
SPECIFICATION
| Model | DTH33-10KL | DTH33-10KS | DTH33-15KL | DTH33-20KL | DTH33-20KS | DTH33-25KL | DTH33-30KL | DTH33-30KS | DTH33-40KS | |
| Capacity | 10kVA | 10kVA | 15kVA | 20kVA | 20kVA | 25kVA | 30kVA | 30kVA | 40kVA | |
| Input | ||||||||||
| Rated Voltage | (3 phase+N+PE) 380/400/415VAC | |||||||||
| Voltage Range | 305~477VAC | |||||||||
| Frequency Range | 40~70Hz | |||||||||
| Power Factor | ≥0.99@100% load | |||||||||
| THDi | <3%(100% linear load);<5%(100% nonlinear load) | |||||||||
| Output | ||||||||||
| Voltage | 380/400/415VAC(3 Phase+N) | |||||||||
| Voltage Accuracy | ±1% | |||||||||
| THDu | ≤2%(100% linear load),≤4%(100% nonlinear load) | |||||||||
| Power Factor | 1.0 | 0.9(optional 1.0) | 1.0 | |||||||
| Frequency Range | Synchronization Range | Default: ±2Hz;±0.5Hz,±1Hz,±3Hz(configurable) | ||||||||
| Battery Mode | 50Hz±0.1Hz or 60Hz±0.1Hz | |||||||||
| Overload | <105%,long run;105%~110%,60min;110~125%,10min;>125~150%,1min;>150%,0.2s | |||||||||
| Creat Factor | 3:1 | |||||||||
| Switching Time | 0ms | |||||||||
| Efficiency | ||||||||||
| Inverter Mode | 95% | |||||||||
| ECO Mode | 99% | |||||||||
| Battery | ||||||||||
| Voltage | KL:±192VDC,±180~±264V(30~44 units configurable) with neutral wire KS:10~30kVA,allowing up to 60 units/2 sets 40kVA: allowing up to 80 units/2 sets | |||||||||
| System | ||||||||||
| Display | 5" LCD touch screen | 7" LCD touch screen | ||||||||
| Communication | RS232, RS485, dry contact, intelligent slot | |||||||||
| Environment | ||||||||||
| Operating Temperature | 0~40℃(battery life will be shorten when temperature >25℃) | |||||||||
| Humidity | 0~95% (non-condensing) | |||||||||
| Altitude | 1000m no derate, >1000m derate 1% per 100m | |||||||||
| Noise | ≤60dB (A)@1m | |||||||||
| Protection Class | IP20 | |||||||||
| Physical | ||||||||||
| W*D*H(mm) | 280*685*725 | 400*686*1100 | 280*685*725 | 280*685*725 | 400*686*1100 | 280*685*725 | 280*685*725 | 400*686*1100 | 425*780*1600 | |
| Weight(kg) | 45 | 55 | 45 | 45 | 55 | 45 | 45 | 55 | 128 | |