Features
Supports hot standby for parallel machines, N+X redundant parallel operation, providing highly reliable power.
Optional monitoring protocols compatible with backend power device monitoring, featuring user-friendly monitoring functions.
Humanized control design with no strict operating sequence, ensuring simple and safe usage.
Stable and reliable power supply.
Specification
| Model | XMI3105D(R/P) | XMI31075D(R/P) | XMI3108D(R/P) | XMI3110D(R/P) | XMI3115D(R/P) | XMI3120D(R/P) |
| Capacity | 5kVA | 7.5kVA | 8kVA | 10kVA | 15kVA | 20kVA |
| Input | ||||||
| Rated Voltage | 380Vac | |||||
| Voltage Range | Phase voltage (285~475) Vac | |||||
| Frequency Range | (50 ± 5%)Hz | |||||
| Rated DC Voltage | 110/220Vdc | 220Vdc | ||||
| Output | ||||||
| Rated Voltage | Single phase 220Vac | |||||
| Voltage Accuracy | (220 ± 1%)Vac | |||||
| Output Frequency | (50 ± 0.5%)Hz | |||||
| Power Factor | 0.8 | |||||
| THDu | <3% (linear full load), <5% (non-linear full load) | |||||
| Overload Capacity | 105%~125%, switch to bypass in 10 min; 125%~150%, switch to bypass in 1 min; >150%, immediately switch to bypass | |||||
| Switching Time | 0ms | |||||
| Current imbalance in parallel operation | ≤5% | |||||
| Protection | ||||||
| Overload | Switch to bypass power supply, automatically switch to mains power after load reduction | |||||
| Overheat | >85℃, switch to bypass power supply | |||||
| Short Circuit | Inverter shutdown with protection alarm | |||||
| Fault | Switch to bypass with protection alarm | |||||
| Undervoltage | Automatic shutdown | |||||
| Display | ||||||
| LED Indication | AC power indicator, inverter indicator, bypass indicator, DC undervoltage indicator, overload indicator, fault indicator | |||||
| LCD Display | AC input/output voltage, AC input/output frequency, DC input voltage, load precentage, apparent power, active power, output current, UPS operating status | |||||
| Other Function | ||||||
| Alarm | Input abnormality, low battery voltage, overload, and other error | |||||
| Communication | Standard RS-232/RS485 (supporting Modbus protocol), dry contact; SNMP remote monitoring (optional) | |||||
| Environment | ||||||
| Operating Temperature | (-5 ~ 40)℃ | |||||
| Relative Humidity | 0~95% (no condensation) | |||||
| Noise | <55dB @ 1 meter | |||||
| Mechanical Indicators | ||||||
| Rack-mount with internal transformer width x depth x height (mm) | 440 x 470 x 712(16U) | 440 x 470 x 712(16U) | ||||
| Rack-mount with external transformer width x depth x height (mm) | 482 x 440 x 264(6U) | 482 x 440 x 264(6U DC220V) 440 x 440 x 311(7U DC110V) | 482 x 440 x 264(6U) | 440 x 440 x 355(8U) | ||
| Rack-mount weight (kg) | 22 (external) | 100 (internal) 28/30 (external) | 142 (internal) 28/30 (external) | 145 (internal) 28/30(external) | 160 (internal) 28 (external) | 35(external) |
| The product is subject to the actual item. The above specifications are subject to change without prior notice. | ||||||