◆FEATURE

Efficient And Energy-Saving
*The input power factor is above 0.99;
*The fan can be intelligently adjusted at multiple levels according to the load and temperature;
* The efficiency of battery mode is more than 90%, and that of utility mode is more than 99%.

Flexible Use And Strong Environmental Applicability
* Modular expandable design, supporting up to 5 modules in parallel,
Standard 19-inch rack structure, supporting embedded installation and flexible
*Strong overload capacity, supporting 150% rated load impact operation, applicable to non-linear communication equipments;
* Automatic start and DC cold start, realizing unattended
Intelligent Monitoring Management Function
*Standard RS485 communication interface
*Dry contact communication interface, including mains power failure and system alarm interface;
SPECIFICATION
| Model | XMI30DGR | XMI60DGR | XMI9ODGR | XMI120DGR | XMI150DGR |
| Rate Capacity | 3kVA | 6kVA | 9kVA | 12kVA | 15kVA |
| Input | |||||
| Voltage Range | 165~260Vas | ||||
| Frequency Range | 50±5%Hz | ||||
| Power Factor | ≥0.99 | ||||
| DC Input | |||||
| Rated Voltage | Default 240VDC (220VDC can be set) | ||||
| Voltage Range | 196~286VDC | ||||
| Battery Type | Lead acid battery | ||||
| AC Output | |||||
| Rated Voltage | 220Vac | ||||
| Voltage Range | 220±2%Vac | ||||
| Power Factor | 0.8 | ||||
| Rated Frequency | 50Hz | ||||
| Frequency Range | A9-51Hz | ||||
| Voltage Waveform Distortion | ≤3%(resistive load) | ||||
| Efficiency | ≥90% | ||||
| Overload Capacity | 105%<Load<125%:maintain for 10 minutes;125%≤Load<150%:maintain for 1 minute;Load≥150%:immediate protection | ||||
| Switching Time | |||||
| Mains--Inverter Switching Time | ≤10ms | ||||
| Protection Characteristics | |||||
| Mains Input Undervoltage Switching | ≤176Vac | ||||
| Output overvoltage protection | ≥245Vac | ||||
| Battery Low Voltage Alarm | <200Nac | ||||
| Output short circuit protection | Have | ||||
| Battery reverse connection protection | Have | ||||
| Communication | |||||
| Communication interface | RS485、Dry contact | ||||
| Environment | |||||
| Working altitude | The altitude shall not exceed 1000m,and the derating shall be more than 1000m.Refer to IEC62040 | ||||
| working temperature | -5~40°℃ | ||||
| Working relative humidity | 0~95%(no condensation) | ||||
| Working noise | <65dB @1m | ||||
| Mechanical Index | |||||
| Wide(mm) | 482.6 | 482.6 | 482.6 | 482.6 | 482.6 |
| Deep(mm) | 350 | 350 | 350 | 350 | 350 |
| High (mm) | 44.5(1U) | 88(2U) | 132(3U) | 176(4U) | 220(5U) |