ABOUT HQ33 INDUSTRIAL BACKUP POWER ONLINE UPS
Applications: Medical equipment, computer equipment, data center, precision instrument, bank, highway toll systems, productionlines&controlling system.
◆FEATURE

Safe and Reliable
*N+1 redundant cooling system
*Built-in manual maintenance bypass switch
*Output isolation transformer
*Allowing for 3 phase 100% unbalanced load
*Isolated air duct design
*Employing phase-locked loop technology alongside electronic static bypass switch
Comprehensive Protection
*Overvoltage, undervoltage, low battery voltage warning
*High-speed DSP and programmable components
*Eddy current fan
*Battery units configurable
*10-80kVA support cold start function
Intelligent Management
*Automated self-testing
*Surge/overload/short circuit/overheat protection
*7" Color touch screen display multiple languages
*Support RS232/RS485, SNMP optional
*Parameters and status display in real-time on the PC
◆OTHER
Built-in maintainance bypass switch
Surge/overload/short circuit/overheat protection
Output isolation transformer included
Capacity: 10kVA-600kVA
SPECIFICATION
| Model | HQ3310L | HQ3320L | HQ3330L |
| Capacity | 10kVA | 20kVA | 30kVA |
| Input | |||
| Related Voltage | 380/400/415VAC, 3 Phase+N+PE | ||
| Voltage Range | ±25% | ||
| Rated Frequency | 50/60Hz(auto-sensing) | ||
| Frequency Range | 40~70Hz | ||
| Bypass | |||
| Ralted Voltage | 380/400/415VAC | ||
| Rated Frequency Range | ±10%(±5% configurable) | ||
| Rated Frequency | 50/60Hz | ||
| Inverter/Bypass Switch | 0ms | ||
| Output | |||
| Power Factor | 0.9 | ||
| Rated Voltage | 380/440/415VAC, 3 Phase+N+PE | ||
| Phase Voltage | 220(200~244V configurable) | ||
| Creat Factor | 3:1 | ||
| THDu | <2% @100% linear load;<5% @100% non-linear load | ||
| Voltage Accuracy | ±1% | ||
| Transient Response | ±5%<10ms | ||
| Overload | 125%,10min;150%,1min | ||
| Efficiency | ≥93% @ 100% load | ||
| Battery | |||
| Voltage | 360~408V (30-34 units configurable) no neutral wire | ||
| System | |||
| Communication | RS232, RS485, optional: dry contact, SNMP | ||
| Operating Temperature | -10~40℃ | ||
| Display | 7" touch screen | ||
| Humidity | 0~95℃(non-condensing) | ||
| Altitude | <1000m no derate,>1000m derating 1% 100m | ||
| Noise | ≤65dB @ 1m | ||
| Physical | |||
| W*D*H(mm) | 500*600*1250 | ||
| Weight(kg) | 187 | 230 | 260 |