ABOUT HQ-M 60-120KVA ONLINE RACKMOUNT MODULAR UPS
This scalable UPS can be widely used in postal communications, financial securities, government agencies, energy and chemical industry, transportation, industrial and commercial taxation, medical and health, national defense and military and other electrical equipment that require reliable power supply.
◆FEATURE

Modular design
The cabinet can be configured with up to 7 main power modules; the modular design of the system can be designed according to future system needs, and the modules can be configured according to the existing load, significantly reducing one-time investment costs.

High Reliability
*Distributed control system for power module
*Isolated air duct for key components
*BMS monitors battery information in real time
*Online UPS: online double conversion

Green Performance
*Efficiency up to 96%
*Output PF = 1
*Maintenance bypass mode
*THDi < 3% and input PF > 0.99
◆OTHER
Offering scalability for easy expansion or reduction of capacity
Rack-mountable for optimized space efficiency
Capacity: 40kVA/50kVA/80kVA/100kVA/120kVA/150kVA
Topology: online double conversion
Specification
| Model | HQ-M80 | HQ-M100 | HQ-M140 | HQ-M175 | HQ-M240 | HQ-M300 |
| Rated Capacity | 80kVA | 100kVA | 140kVA | 175kVA | 240kVA | 300kVA |
| Power Module Capacity | 20kVA | 25kVA | 20kVA | 25kVA | 20kVA | 25kVA |
| Power Module Quantity | 4 | 7 | 12 | |||
| Input | ||||||
| Wiring Method | 3 Phase+N+PE | |||||
| Rated Voltage | 380/400/415VAC(line-line) | |||||
| Rated Frequency | 50/60Hz | |||||
| Voltage Range | 304VAC~478VAC(line-line) full load; 304VAC~228VAC(line-line), loading derating linearly from 100% to 80% | |||||
| Frequency Range | 40Hz~70Hz | |||||
| Power Factor | >0.99 | |||||
| THDi | <3%(linear full load);<5%(non-linear full load) | |||||
| Bypass | ||||||
| Rated Voltage | 380/400/415VAC(line voltage) | |||||
| Voltage Range | Factory setting -20%~+15%; settable, upper limit:+10%,+15%,+20%,+25%; lower limit:-10%,-15%,-20%,-30%,-40% | |||||
| Frequency Range | Rated frequency 50/60Hz;frequency range can be set ±0.5Hz, ±1Hz, ±2Hz, ±3Hz, ±10Hz(by default) | |||||
| Overload Capacity | 110% for long run; >150% for 200ms | |||||
| Battery | ||||||
| Battery Voltage | ±192VDC(360~528VDC;30~44 units settable, defaulted by 32 units) | |||||
| Output | ||||||
| Rated Voltage | 380/400/415VAC(line voltage) | |||||
| Rated Frequency | 50/60Hz | |||||
| Power Factor | 1 | |||||
| Voltage Accuracy | ≤±1.0%@balanced load;≤±5.0%@unbalanced load | |||||
| Frequency Accuracy | 50/60Hz±0.01% | |||||
| Frequency Tracking Range | Settable, ±0.5Hz~±5Hz;±3Hz | |||||
| THDu | ≤2%(100% linear load),≤4%(nonlinear load) | |||||
| Three-phase Phase Accuracy | 120°±1° | |||||
| Crest Factor | 3:1 | |||||
| Overload | <105%, long run; <110%, 60mins; 110~125%, 10mins;>125~150%, 1mins;>150%, 200ms | |||||
| System | ||||||
| System Efficiency | ≥96%@double conversion mode,≥99%@ECO mode | |||||
| Display | 7" touch screen+LCD | |||||
| Wiring | Bottom in | Top in and bottom in | Top in | |||
| Standard | IEC62040-1-1;IEC62040-2;IEC62040-3 | |||||
| Protection Class | IP20 | |||||
| Feeder Protection | Standard:isolating switch, optional:fuse | |||||
| Communication | RS232/RS485/SNMP(optional)/Dry contact card(optional) | |||||
| Optional | Dust-proof net, lightning protection module, LBS cable, earthquake-proof components, temperature and humidity sensor | |||||
| Working Condition | Temperature:0~40℃;humidity: 0~95℃(no condensation) | |||||
| Noise | <65dB@1 meter | |||||
| Altitude | <1000 meters, no derating,>1000 meters, derating 1% if every 100 meters increased | |||||
| Cabinet Type | 4 Modules | 7 Modules | 12 Modules | |||
| Size | ||||||
| System W*D*H(mm) | 600*850*1200 | 600*850*1600 | 600*1010*2000 | |||
| Module W*D*H(MM) | 440*690*86(2U) | |||||
| Weight | ||||||
| System(kg) | 145 | 210 | 239 | |||
| Module(kg) | 24(20kVA), 25(25kVA) | |||||