ABOUT XMI PURE SINE WAVE TELECOM INVERTER
EVADA XMI Pure Sine Wave Telecom Inverter is meticulously crafted to meet the rigorous demands of telecom applications. With its pure sine wave output, this inverter ensures the integrity of sensitive telecom equipment, delivering stable and reliable power for communication services. Designed with precision, it incorporates 90% efficiency, 3% harmonic distortion, and precise voltage regulation, guaranteeing peak performance in demanding telecom environments.
◆FEATURE
Intelligent Flexibility
*N+X redundant parallel technology
*Masterless current sharing allows high-precision load sharing*Direct use of DC system
High Reliability
*Noise suppression technology
*Online structure design
*Relay + SCR compensation and flashover protection
*AC and DC double loop input design
Intelligent Monitoring System
*Supports RS485/RS232 interface and SNMP(optional)
◆OTHER
Total harmonic distortion≤3%
Input DC voltage: 48VDC, DC output voltage: -48VDC (pure inverter without DC output)
SPECIFICATION
| Model | XMI10HR-X | XMI20HR-X | XMI30HR-X | |
| Capacity | 1kVA | 2kVA | 3kVA | |
| Input | ||||
| AC Voltage | 176~250VAC(configurable) | |||
| Frequency | 50Hz±5% | |||
| Power Factor | ≥0.99 | |||
| Rated Voltage | 48VDC | |||
| Battery Voltage Range | 43~60VDC | |||
| AC Output | ||||
| Power Factor | 0.8 | |||
| Voltage | 220VAC±2%(inverter mode) | |||
| Efficiency | ≥90%(inverter mode) | |||
| Frequency | 49~51Hz | |||
| Waveform | Puresine wave(inverter mode) | |||
| THDu | ≤3%(linear load under full load) | |||
| Overload | 125% rated load 10 min; 150% rated load 1 min | |||
| Switching Time | ≤10ms | |||
| DC Output | ||||
| Voltage | 54.5~57.6VDC | |||
| Current | Optional rectifier module: 0A/6A/30A(6A charging)/30A | Optional rectifier module: 0A/10A/30A(6A charging)/30A | ||
| Protection | ||||
| Bypass Inverter | Low-voltage switching point | 176±3Vac | ||
| High-voltage switching point | 265±3Vac | |||
| Inverter Bypass | Low-voltage recovery point | 186±3Vac | ||
| High-voltage recovery point | 255±3Vac | |||
| Battery low-voltage warning point | 43±0.5Vdc | |||
| Battery undervoltage protection point | ≤40Vdc | |||
| Battery overvoltage protection point | ≥60Vdc | |||
| Battery overvoltage recovery point | ≥55Vdc | |||
| Output overcurrent protection | 100%~135%:protection after 10 mins | |||
| 125%~150%: protection after 1 min | ||||
| >150%: instant protection | ||||
| Output shortcircuit protection | Yes(short circuit is prohibited when grid power is connected) | |||
| Battery reverse protection | Yes(models with charging function prohibit reverse polarity connection) | |||
| Overheat protection | Yes(automatic recovery after fault condition is cleared) | |||
| Cooling method | Built-in fan cooling(intelligent speed control) | |||
| System | ||||
| Display | LCD, LED(optional) | |||
| Communication | RS485, dry contact | |||
| Physical | ||||
| W*D*H(mm) | 482*350*44 | |||
| Weight(kg) | 6.2 | |||
| *Specifications subject to change without notice | ||||